Pilot Operated Proportional DC Valve
Series D*1FC
3
Catalogue HY11-3500/UK
Parker Hannifin Corporation
Hydraulics Group
Technical Data / Characteristic Curves
Electrical characteristics
Duty ratio [%] 100
Protection class IP65 in accordance with EN 60529 (with correctly mounted plug-in connector)
Supply voltage/ripple DC [V] 18...30, electric shut-off at < 17, ripple < 5 % eff., surge free
Current consumption max. [A] 2.0
Pre fusing medium lag [A] 2.5
Command signal
Code K (B) Voltage
Impedance
Code E Current
Impedance
Code S Current
[V]
[kOhm]
[mA]
[Ohm]
[mA]
10...0...-10, ripple <0.01 % eff., surge free, 0...+10 V P—>A (P—>B)
100
20...0...-20, ripple <0.01 % eff., surge free, 0...+20 mA P—>B
200
4...12...20, ripple <0.01 % eff., surge free, 12...20 mA P—>A
< 3.6 mA = enable off, > 3.8 mA = enable on acc. to NAMUR NE43
Impedance [Ohm] 200
Differential input max.
Code 0/7
Code 5
[V]
30 for terminal D and E against PE (terminal G)
11 for terminal D and E against 0 V (terminal B)
30 for terminal 4 and 5 against PE (terminal PE)
11 for terminal 4 and 5 against 0 V (terminal 2)
Adjustment ranges Min [%] 0...50
Max [%] 50...100
Ramp [s] 0...32.5
Interface RS 232, parametrizing connection 5pole
Enable signal (code 5/7) [V] 5...30
Diagnostic signal [V] +10...0...-10 / +12.5 error detection, rated max. 5 mA
EMC EN 61000-6-2, EN 61000-6-4
Electrical connection Code 0/7
Code 5
6 + PE acc. to EN 175201-804
11 + PE acc. to EN 175201-804
Wiring min. [mm²] 7 x 1.0 (AWG16) overall braid shield
Wiring length max. [m] 50
All characteristic curves measured with HLP46 at 50 °C.
Electrical characteristics hybrid option
Duty ratio [%] 100
Protection class IP 65 in accordance with EN 60529 (with correctly mounted plug-in connector)
Supply voltage [V] 24
Tolerance supply voltage [%] ±10
Current consumption [A] 1.21
Power consumption [W] 29
Solenoid connection Connector as per EN 175301-803
Wiring min. [mm²] 3 x 1.5 recommended
Wiring length max. [m] 50 recommended
With electrical connections the protective conductor (PE W) must be connected according to the relevant regulations.
D41FC
Spool code E01, E02, B31, B32
D*1FC B/E Flow characteristics
(set to opening point 10 %)
at Dp = 5 bar per metering edge
D31FC
Spool code E01, E02, B31, B32